I experienced a sub panel installed today fed with a 60 amp breaker yet they provided a key panel for the below panel rather of a main lug only type. They kept the 100 amp breaker in the below to usage as the disconnect. Is this allowed or have to it it is in swapped because that a 60 amp breaker to enhance the main?Another concern also. I saw a dashboard in a bathroom yet there was complete size door choose a closet that covered the panel. The door likewise had a rubber seal at the bottom that it. Is this acceptable? It to be a 3 year old home.
*

I experienced a below panel mounted today fed through a 60 amp breaker yet they used a main panel because that the below panel rather of a key lug only type. They kept the 100 amp breaker in the sub to usage as the disconnect. Is this allowed or should it be swapped because that a 60 amp breaker to complement the main?Another question also. I observed a panel in a bathroom yet there was full size door choose a closet that spanned the panel. The door likewise had a rubber seal in ~ the bottom of it. Is this acceptable? It to be a 3 year old home.
The breaker is fine. The wire is protected by the 60 amp main, the 100 amp in the sub will never trip and is not also required.The dashboard in the bathroom, i say no. If it to be in a different room than it’s ok, but installing a door in prior of it to me does not adjust the truth that it is in a bathroom.
*

I experienced a below panel mounted today fed with a 60 amp breaker but they supplied a key panel for the sub panel instead of a key lug just type. They kept the 100 amp breaker in the below to use as the disconnect. Is this permitted or need to it it is in swapped for a 60 amp breaker to complement the main?Another concern also. I observed a dashboard in a bathroom but there was complete size door like a closet that extended the panel. The door additionally had a rubber seal in ~ the bottom that it. Is this acceptable? It was a 3 year old home.

See more: Where To Get Hm Dive In Emerald, Where Can I Find The Hm Dive


Using the 100 amp key breaker together a disconnecting method for a sub-panel is okay, since the OCPD is 60 amps at the main panel. In this instance, it"ll simply be a disconnect for you to job-related in the panel and see the disconnecting method in the off/open position.As much as panels in a bathroom, also with a waterproof/water resistant door, the is an undesirable location and should not be set up there.Sent from mine Samsung utilizing Tapatalk
*

While I often tend to agree regarding the panel, I think that I witnessed somewhere over the years the a panel install choose this is acceptable.Since it has actually a full size door it is taken into consideration not part of the bathroom; think that a bedroom v an en suite. Now as long as it is not a closet or deep enough to keep things in prior of the is great to go.It would certainly not it is in my first choice, but I think it is acceptable.CheersJohn
*
Reactions:billyhunter and also The_Modifier